The Calculation, Explained
The derivation
Everything follows from one balance: fuel energy in = electrical energy out / efficiency, and heat rate is efficiency in disguise.
Volume flow needs the gas density at the reference state. This calculator uses normal conditions (0 °C, 1.01325 bar), where air density is 1.293 kg/m³, so ρgas = SG × 1.293:
MMSCFD converts the daily volume to cubic feet (1 ft³ = 0.0283168 m³); MMBTU/h converts thermal power at 1 MW = 3.41214 MMBTU/h.
Assumptions and applicability
- Normal vs standard — read this before comparing with a bill. Gas is also commonly metered at 15 °C ("standard" m³, Sm³) or 60 °F. The same gas occupies 5.4% more volume at 15 °C than at 0 °C. A flow that "disagrees" with the fiscal meter by ~5% is often just two different reference temperatures arguing with each other.
- Ideal-gas behaviour is assumed in the density conversion — adequate at near-atmospheric reference conditions, which is where reference volumes are defined.
- The heat rate and the LHV must be on the same basis (both LHV here). An HHV heat rate with an LHV heating value silently invents or destroys ~10% of the fuel.
- Steady operation at the stated output; start-up, shutdown and ramping fuel are outside this balance.
Worked example (the defaults above)
An 850 MW plant at 9,850 kJ/kWh: thermal input = 850 × 9,850 / 3,600 = 2,325.7 MW thermal. At LHV 49.0 MJ/kg, mass flow = 2,325,700 / 49,000 = 47.5 kg/s (170.9 t/h). At SG 0.60 (ρ = 0.776 kg/Nm³): ≈ 220,000 Nm³/h, i.e. ≈ 187 MMSCFD, or 7,936 MMBTU/h. If the station meter reads far from these numbers at this load, either the meter, the heat rate, or the LHV is wrong — and finding out which is exactly what test day is for.
References
ASME PTC 46 (test boundary and fuel measurement); ISO 6976 (heating values from composition — see the companion Gas Heating Value & Wobbe Index calculator for the LHV and SG of your actual gas).
Related calculators: Gas Heating Value & Wobbe · Heat Rate & Efficiency